Technical parameters | ||||
Name | Main Technical Parameters | |||
Genset model | CCFJ250J-W2 | |||
Power supply type | Three-phase AC | |||
Rated power kW | 250 | |||
Rated voltage V | 400 | |||
Rated current A | 451.1 | |||
Rated frequency (Hz) | 50 | |||
Rated power factor(COSφ) | 0.8(Lag) | |||
Rated speed r/min | 1500 | |||
Absolute value of steady-state voltage regulation % | ≤2.5 | |||
Absolute value of transient voltage deviation (%) | Sudden unloading 60% Rated current | ≤20 | ||
Sudden load 60% Rated current | ≤15 | |||
Voltage stabilization time (s) | ≤1.5 | |||
Absolute value of voltage fluctuation rate % | ≤1 | |||
Absolute value of transient speed regulation % | Sudden load 0-50% | ≤10 | ||
Sudden load 50-100% | ||||
Sudden unloading 100%-0 | ||||
Transient speed regulation stabilization time (s) | ≤5 | |||
Steady-state speed regulation % | ≤5 | |||
Absolute value of speed fluctuation rate% | ≤0.5 | |||
Insensitivity of genset speed governing system % | ≤0.5 | |||
Fuel consumption rate under rated conditions (g/(kW·h))) | ≤205 | |||
Specific oil consumption g/(kW·h) | ≤0.35 | |||
Fuel grade | Summer: 0#, 10# light diesel of GB 19147-2016 premium grade or first grade;; | |||
Winter: 0#, -10#, -20# and -35# light diesel of GB 19147-2016 premium grade or first grade (selected based on the ambient temperature)) | ||||
Oil grade | Summer: 40CF, 15W/40CF; | |||
Winter: 30CD, 10W/30CD or other diesel engine oil that is not inferior to Grade CF in GB 11122-2006 and suitable for the environment. | ||||
Start mode | Electric start | |||
Cooling mode | Internal circulation:Closed circulating water cooling,External circulation:Open water cooling | |||
Connection mode of motor winding | Three-phase four-wire | |||
Operating mode of genset | Continuous | |||
Operating environment conditions | Ambient temperature | 45°C | ||
Outboard water temperature | 32°C | |||
Inclination angle | Hell: 15°; roll: 22.5°; trim: 7.5°; pitch: 10° | |||
Temperature rise | Thermal classificationA | 55°C | ||
Measurement method R | ||||
Short circuit | The alternator and its excitation system can maintain at least 3 times the rated current for at least 2s under steady-state short-circuit conditions. | |||
Overload | 50% overcurrent; 2 min | |||
Fuel engine model | YC6MJ410L-C24 | |||
Rated power of diesel engine (kW) | 300 | |||
Alternator model | SB-HW4.D-250 | |||
(SAE1-14) | ||||
Rated power of motor (kW) | 250 | |||
Genset weight (kg) | 2120 | |||
Diemension(Length × width × height) mm | 2500×1035×1385 | |||
Note: Dimension (L*W*H) may vary with the configuration. |