Customization: | Available |
---|---|
After-sales Service: | Schedule |
Warranty: | Schedule |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Genset model | YC280GF | YC300GF | |
Prime power (KW/kVA) | 280/350 | 300/375 | |
Standby power (KW/kVA) | 300/375 | 330/412 | |
Rated voltage V | 400/230 | ||
Rated currency A | 451 | 542 | |
Frequency | 50 | ||
Power factor | 0.8 | ||
Frequency drop % | ≤2 | ||
Steady state frequency band | ≤0.5 | ||
(For rated frequency) Transient frequency deviation % | 100%The sudden | ≤+10 | |
reduction power | |||
Sudden load power | ≤-7 | ||
Recovery frequency time ( s ) | ≤3 | ||
Steady state voltage deviation % | ≤±1 | ||
Transient voltage | 100%The sudden | ≤+20 | |
deviation% | reduction power | ||
Sudden load power | ≤-15 | ||
Voltage recovery time ( S ) | ≤3 | ||
Voltage unbalance degree % | ≤1 | ||
Genset dimension(mm)/Weight (kg) | 3000x11200x1700/2200 | 3100x1130x1810/2400 | |
Engine | Model | YC6MJ480L-D20 | YC6MJ500-D21 |
Prime power(KW) | 321 | 335 | |
Standby power(KW) | 352 | 370 | |
Brand/manufacture | YUCHAI | ||
Speed(r/min) | 1500 | ||
No. of Cylinder | 6 | ||
Cylinder arrangement | L | ||
Stroke | Four stroke | ||
Air intake mode | Turbocharged | ||
Fuel supply | electronic regulation | ||
Bore x stroke | 131×145mm | ||
Displacement | 11.726L | ||
Emission | No-roadT2(optionT3) |